Posted 12/27/2005 7:32:28 PM
Supreme Being

Supreme BeingSupreme BeingSupreme BeingSupreme BeingSupreme BeingSupreme BeingSupreme BeingSupreme Being

Group: Forum Members
Last Login: 6/18/2008 10:17:32 AM
Posts: 98, Visits: 161
We have a odor problem at are head works. We have an enclosed wet well at our main pump station. Considered using pre aeration but afraid of corrosion from the release of sulfides. Would likely have to enclose and install some kind of ventallation or scrubber? What are the minus and plus of using cl2?
Post #701
Posted 1/4/2006 12:58:32 PM
Forum Newbie

Forum NewbieForum NewbieForum NewbieForum NewbieForum NewbieForum NewbieForum NewbieForum Newbie

Group: Forum Members
Last Login: 4/3/2006 5:02:35 PM
Posts: 6, Visits: 24
may not have too much operational problem, but you would need to meet all regulatory requirements for storage.  if you really have high h2s concentration and stringent removal requirement, you may also need to use caustic.  this chemical may give you some problem.
Post #746
Posted 1/4/2006 4:47:20 PM
Forum Member

Forum MemberForum MemberForum MemberForum MemberForum MemberForum MemberForum MemberForum Member

Group: Forum Members
Last Login: 6/19/2008 12:52:53 PM
Posts: 32, Visits: 91
If you are willing to consider an alternative to chlorine, which will handle both odor and corrosion related issues, you might want to consider using Magnesium Hydroxide. It's exceptionally good at eliminating odors, and can also reduce corrosion.  It's safe and easy to handle.  We've been using it at our facility for a couple of years.  It's a really great product. 

Mary

Post #748
Posted 1/5/2006 12:55:33 PM
Supreme Being

Supreme BeingSupreme BeingSupreme BeingSupreme BeingSupreme BeingSupreme BeingSupreme BeingSupreme Being

Group: Forum Members
Last Login: 8/5/2008 5:28:31 PM
Posts: 372, Visits: 721
Significant addition of mag hydroxide could result in production of magnesium ammonium phosphate, if you have anaerobic digesters.

David
Post #754
Posted 1/5/2006 5:32:54 PM
Supreme Being

Supreme BeingSupreme BeingSupreme BeingSupreme BeingSupreme BeingSupreme BeingSupreme BeingSupreme Being

Group: Forum Members
Last Login: 6/26/2008 4:01:08 PM
Posts: 156, Visits: 1,477
A couple of thoughts: if you go the route of a vent and scrubber, you may need to register it as an air emissions point (especially if there is a odor treatment process involved) with your State regulators.  What (if any) monitoring would be required can vary, but will need to factor in time for paperwork, data collection, etc. Give them a call to find out what applies in your area. Second: I've seen a few wet well situations where odors were created because the ventilation system had an exhaust only (apparantly assuming that fresh air would enter from the hatchway or door), while in reality, the fan was drawing gasses from down the influent sewer. A big help was to convert to a positive pressure system, i.e., a fan blowing outside air into the wet well at a rate higher than the exhaust fan. The excess pressure keeps at least some of the odors in the sewer.
Post #761
Posted 2/15/2008 8:05:45 PM
Forum Newbie

Forum NewbieForum NewbieForum NewbieForum NewbieForum NewbieForum NewbieForum NewbieForum Newbie

Group: Forum Members
Last Login: 6/17/2008 11:03:45 PM
Posts: 1, Visits: 6
Consider using Magnesium Hydroxide in a master lift station before it gets to the plant.  There is a plus.  pH around 8.5 which locks in the hydrogen sulfide and great alkalinity which will improve treatment in the plant
Post #8402
« Prev Topic | Next Topic »

Reading This TopicExpand / Collapse
Active Users: 1 (1 guest, 0 members, 0 anonymous members)
No members currently viewing this topic.

PermissionsExpand / Collapse

All times are GMT -5:00, Time now is 3:14pm

Powered By InstantForum.NET v4.0.0 © 2008
Execution: 0.141. 10 queries. Compression Enabled.